Storefront Air & Water Performance Testing in Colorado
Project type: Nonresidential building · Service: Independent field performance testing
The Project Need
A project team required documented field performance testing of installed aluminum storefront window systems. The scope addressed air leakage and water penetration performance against the applicable project criteria.
BEF’s Role
Building Enclosure Forensics performed field testing in accordance with ASTM E783, ASTM E1105, and AAMA 501.2, as identified in the project report. BEF recorded specimen-specific observations and test results in a written report for the client.
The Documented Result
The evaluated air leakage specimens were below the specified maximum allowable leakage. No water leakage was observed during the reported ASTM E1105 tests or AAMA 501.2 field checks. The tested specimens satisfied the applicable criteria under the conditions evaluated.
What the Results Establish
The report provides a record of the tested assemblies and conditions. It does not certify a product, endorse a manufacturer, or establish the performance of every assembly in the building under all conditions.
This summary is anonymized. Client and facility identities, addresses, costs, specimen locations, detailed procedures, and repair recommendations are not published.